GSW Class 70kW-200kW Perkins |
|

Milbank PowerGen|Generators proudly announces the Industrial Standby Generator line of water cooled Perkins 70kW - 200kW models.
This series provides a versatile and highly reliable solution to a variety of applications.
Features
- STAMFORD alternator
- Water cooled
- Automatic Controller
- Internal residential muffler
- Detachable central lifting point
- Completely sealed drip pan
- Complete with engine and battery liquids
- Manual oil drain pump
- Heavy duty galvanised skids (optional)
- Baseframe can be moved with hand pallet truck
- Standard 8 hour tank (varies by model)
- EPA tier compliant
- ATS, trailers, base tanks among other features available optionally
Models
| | Model Number | GSW70P | GSW90P | GSW120P | GSW160P | GSW200P |
|
|
|
PRIME POWER PRP |
58 kW (73 kVA) |
74 kW (93 kVA) |
91 kW (114 kVA) |
125 kW (156 kVA) |
161 kW (201 kVA) |
| EMER POWER LTP |
64 kW (80 kVA) |
82 kW (103 kVA) |
100 kW (125 kVA) |
142 kW (177 kVA) |
178 kW (223 kVA) |
| Voltage |
480/277 Volt |
480/277 Volt |
480/277 Volt |
480/277 Volt |
480/277 Volt |
| Frequency |
60 Hz |
60 Hz |
60 Hz |
60 Hz |
60 Hz |
| Power factor |
0.8 Cos φ |
0.8 Cos φ |
0.8 Cos φ |
0.8 Cos φ |
0.8 Cos φ |
|
PRIME POWER PRP |
56 kW (70 kVA) |
74 kW (92 kVA) |
90 kW (113 kVA) |
124 kW (155 kVA) |
160 kW (200 kVA) |
| EMER POWER LTP |
58 kW (73 kVA) |
82 kW (102 kVA) |
96 kW (120 kVA) |
140 kW (175 kVA) |
175 kW (219 kVA) |
| Voltage |
208/120 Volt |
208/120 Volt |
208/120 Volt |
208/120 Volt |
208/120 Volt |
| Frequency |
60 Hz |
60 Hz |
60 Hz |
60 Hz |
60 Hz |
| Power factor |
0.8 Cos φ |
0.8 Cos φ |
0.8 Cos φ |
0.8 Cos φ |
0.8 Cos φ |
|
PRIME POWER PRP |
45 kW (45 kVA) |
68 kW (68 kVA) |
68 kW (68 kVA) |
96 kW (96 kVA) |
123 kW (123 kVA) |
| EMER POWER LTP |
50 kW (50 kVA) |
74 kW (74 kVA) |
74 kW (74 kVA) |
106 kW (106 kVA) |
136 kW (136 kVA) |
| Voltage |
240/120 Volt |
240/120 Volt |
240/120 Volt |
240/120 Volt |
240/120 Volt |
| Frequency |
60 Hz |
60 Hz |
60 Hz |
60 Hz |
60 Hz |
| Power factor |
1 Cos φ |
1 Cos φ |
1 Cos φ |
1 Cos φ |
1 Cos φ |
|
Tank capacity |
92 US Gallons |
92 US Gallons |
92 US Gallons |
92 US Gallons |
92 US Gallons |
| Autonomy (III) (75% PRP) |
25.5 h |
21.3 h |
18.1 h |
12.4 h |
9.7 h |
| Autonomy (III) (100% PRP) |
19.1 h |
16 h |
13.6 h |
9.3 h |
7.3 h |
| Dimensions (LxWxH) |
106.7" x 46.5" x 60.4" |
106.7" x 46.5" x 60.4" |
106.7" x 46.5" x 66.3" |
133.9" x 49.2" x 66.1" |
133.9" x 49.2" x 66.1" |
| Weight (dry) |
3,019 lbs |
3,281 lbs |
3,285 lbs |
4,573 lbs |
4,880 lbs |
| DIESEL ENGINE | PERKINS 1104D-E44TG | PERKINS 1104D-E44TAG1 | PERKINS 1104D-E44TAG2 | PERKINS 1106D-E66TAG2 | PERKINS 1106D-E66TAG4 |
| Exhaust emissions |
EPA III |
EPA III |
EPA III |
EPA III |
EPA III |
| Cooling system |
Water |
Water |
Water |
Water |
Water |
| Speed |
1800 rpm |
1800 rpm |
1800 rpm |
1800 rpm |
1800 rpm |
| Displacement |
269.1 cu. in. |
269.1 cu. in. |
269.1 cu. in. |
402.7 cu. in. |
402.7 cu. in. |
| Cylinders and disposition |
4 line n° disp. |
4 line n° disp. |
4 line n° disp. |
6 line n° disp. |
6 line n° disp. |
| Aspiration |
Turbo |
Turbo-Intercooler |
Turbo-Intercooler |
Turbo-Intercooler |
Turbo-Intercooler |
| Engine power PRP |
87 bhp |
110 bhp |
134 bhp |
182 bhp |
233 bhp |
| Engine power LTP |
97 bhp |
122 bhp |
149 bhp |
207 bhp |
259 bhp |
| Fuel cons (III) (75% load PRP) |
3.6 gal/h |
4.3 gal/h |
5.1 gal/h |
7.5 gal/h |
9.5 gal/h |
| Fuel cons. (III) (100% load PRP) |
4.8 gal/h |
5.8 gal/h |
6.8 gal/h |
10 gal/h |
12.7 gal/h |
| Specific consumption PRP |
0.383 lb/hph |
0.363 lb/hph |
0.35 lb/hph |
0.377 lb/hph |
0.376 lb/hph |
| Engine governor (standard) |
Mechanical |
Electronic |
Electronic |
Electronic |
Electronic |
| SYNCH. ALTERNATOR | STAMFORD UCI 224 E | STAMFORD UCI 274 C | STAMFORD UCI 274 C | STAMFORD UCI 274 E | STAMFORD UCI 274 G |
| Power at 27ºC (480V) |
64 Kwe (80 kVA) |
110 Kwe (138 kVA) |
110 Kwe (138 kVA) |
155 Kwe (194 kVA) |
203 Kwe (253 kVA) |
| Power at 27ºC (208V) |
58 Kwe (73 kVA) |
96 Kwe (120 kVA) |
96 Kwe (120 kVA) |
140 Kwe (175 kVA) |
175 Kwe (219 kVA) |
| Power at 27ºC (240V) |
36 Kwe (45 kVA) |
54 Kwe (68 kVA) |
54 Kwe (68 kVA) |
77 Kwe (96 kVA) |
99 Kwe (123 kVA) |
| Insulation |
H |
H |
H |
H |
H |
| Mechanical protection |
IP23 |
IP23 |
IP23 |
IP23 |
IP23 |
| Voltage regulation |
Electronic / 1.0% |
Electronic / 1.0% |
Electronic / 1.0% |
Electronic / 1.0% |
Electronic / 1.0% |
Control Panel
Automatic Control Panel (ACP)
- Automatic control panel mounted on the genset, complete with digital control unit AC01 for monitoring, control and protection of the generating set.
- Instrumentation (Digital) – Generator set voltage (3 phases), Mains voltage, Generator set frequency, Generator set current (3 phases), Battery voltage, Power (kVA - kW - kVAr), Power factor, Hour counter, Engine rpm, Fuel level (%), Engine temperature.
- Commands and Others – Six settings (Automatic test, Automatic starting, Engine locked, Mains contactor forced, Manual start, Genset contactor forced); Emergency stop button; Remote start capable; Acoustic alarm; Integrated battery charger.
- Protections with Alarm – Engine protection (low fuel level, low oil pressure, high engine temperature); Genset protection (under/over voltage, overload, under/over frequency, start failure, under/over battery voltage, battery charge failure).
- Protections with Shutdown – Engine protection (low fuel level, low oil pressure, high engine temperature); Genset protection (under/over voltage, overload, under/over battery voltage, battery charge failure); Circuit breaker and differential protection (optional).
- Output and Sockets – Power cables connected to terminals board (external); main lugs.
* Manual Starting: the preheating period begins automatically when this position is selected. It is necessary to select again this position to enable one more time the preheating period.
Supplements
Genset Supplements
- Note: Some available from factory only.
- APM – PMG for Stamford alternator + MX321 AVR.
- AFP – Automatic fuel transfer pump.
- DCC – Different color canopy.
- EEG – Engine electronic governor.
- PHS – Engine preheat system.
- RCG – Remote control by gsm.
- GSB – Galvanized Skids Frame: Heavy duty galvanized skid to be installed under the genset. Easily transportable with fork lift.
- SUB – Extended capacity sub-base fuel tank.
- ATS – Automatic transfer switch.
- TRL – Road Trailer. Trailer with or without extended run tank.
|